ADA hardware rules, and where buildings fail them.
Opening force, mounting height, operability and closing speed. The requirements are short, specific, measurable — and failed constantly, usually by doors that were compliant once.
The accessibility requirements that apply to door hardware are unusually concrete. Most of them are a number you can measure with a gauge and a stopwatch, which means compliance isn't a matter of opinion — and neither is a failure.
The rules below come from the 2010 ADA Standards for Accessible Design, which adopt much of ICC/ANSI A117.1. Where a state or local code is stricter, the stricter one governs. New York follows the state Building Code, which references A117.1.
Opening force
This is the requirement failed most often, and the one that drifts without anybody touching the door.
- Interior hinged doors: 5 pounds maximum.
- Sliding and folding doors: 5 pounds maximum.
- Exterior hinged doors: the ADA Standards don't set a federal maximum, which surprises people. Many state and local codes do — commonly 8.5 pounds — and fire doors are permitted the minimum force needed to close and latch the assembly.
The force is measured at the latch stile, pushing or pulling the door in its direction of travel. A spring gauge is the tool. What it measures is the closer, and closers drift: fluid thickens in cold weather, valves get turned by whoever was annoyed by the door that week, and the door that passed at installation reads 12 pounds three winters later.
Fire doors are the exception that confuses everyone. A rated door has to latch positively, and that takes force. The standard resolves this by allowing the minimum force required to close and latch — but that isn't a blanket exemption to leave a fire door set as heavy as it will go.
Closer timing
Two separate requirements, both measurable:
- Sweep period: from 90 degrees open to 12 degrees from the latch, the door must take at least 5 seconds. This is the requirement that gives somebody using a walker time to get through.
- Spring hinges: from 70 degrees open to closed, at least 1.5 seconds.
A door that slams fails this, and a slamming door is usually also failing latch adjustment and annoying everybody in the corridor — so it tends to be a complaint before it's a citation.
Hardware height
Operable parts must be mounted between 34 and 48 inches above the finished floor. In practice commercial lock height lands around 38 to 42 inches and is rarely the problem.
Where height does fail: exit device crossbars or touchbars mounted outside the range on non-standard doors, and auxiliary hardware — deadbolts, thumbturns, card readers — added later at whatever height was convenient. If a person has to operate it to get through the door, it's an operable part and the range applies.
Operability — the lever rule
Door hardware must be operable with one hand, without tight grasping, pinching, or twisting of the wrist, and must require no more than 5 pounds of force to operate.
That language is what rules out the round knob. A knob can't be operated without grasping and twisting, so it fails. Levers, push/pull hardware, panic bars and loop handles all pass.
This applies to every operable part on the opening, not just the latch — thumbturns, flush bolts and surface bolts are all caught by the same rule, and flush bolts on a pair are a frequent quiet failure.
Smooth surface at the bottom
The bottom 10 inches of the push side of a door must be smooth, so a wheelchair footrest can push through without catching. Kick plates are the usual solution. Where it fails is protruding hardware in that zone, or a kick plate installed with fasteners that stand proud.
Thresholds
Changes in level at a doorway are limited to 1/2 inch maximum, and anything above 1/4 inch must be beveled no steeper than 1:2. Existing thresholds in older buildings are permitted up to 3/4 inch if beveled. Worn or settled thresholds that exceed this are common in buildings that have had flooring replaced.
The failures that come up most
- Opening force out of range, because the closer was never re-checked after it was installed.
- Sweep period under 5 seconds — the same closer, adjusted for latching and nothing else.
- Knobs still in service, usually on interior doors in older buildings that were never remediated.
- Auxiliary hardware added out of range — a deadbolt at 54 inches, a reader at 56.
- Fire doors treated as fully exempt, set far heavier than they need to be to latch.
- Thresholds that have settled past tolerance after a floor replacement.
Every one of those is correctable with adjustment or a hardware swap. None of them requires replacing the door, which is worth knowing before somebody quotes you a door.