Fire door inspection, documented the way an AHJ wants it.
NFPA 80 requires every fire door assembly to be inspected annually, in writing. Most buildings have never had one done. The inspection is straightforward — it's the documentation that has value when an inspector, an insurer, or a lawyer asks. Serving commercial buildings across Central New York.
What This Covers
20+ Years on Commercial Openings
NFPA 80 requires inspection by someone with knowledge of the operating components of the assembly. It doesn't name a license, which is why inspection quality varies so widely. Performed by someone with more than 20 years on commercial openings, and documented in writing per opening.
Every Rated Opening, Against the Standard
Labels legible, no unlisted modifications, clearances within tolerance, glazing intact, the self-closing device operating from any position, and positive latching. Each opening is checked against the full NFPA 80 criteria, not a glance and a signature.
A Written Record You Can Produce
Each opening identified, dated, with what was found, what was corrected on the spot, and what still needs work. That record is what satisfies the AHJ and what protects you in an insurance audit or a claim. An inspection with no paperwork helps in none of those situations.
Deficiencies Corrected, Not Just Listed
Most of what fails is adjustment rather than replacement — a closer that no longer latches the door, a strike that has drifted, a gap that has grown. Where it can be fixed during the visit it is, and the record shows it corrected rather than outstanding.
A door that closes but doesn't latch isn't a fire door.
It's the single most common failure found, and usually the cheapest to correct. Under fire pressure a door that hasn't latched will open, which is the whole reason the requirement exists.
Symptoms Worth a Second Look
- No written inspection record for the building, or none since before the last renovation
- Rated doors held open on wedges, hooks, or disconnected closer arms
- Labels painted over during a corridor repaint
- Open holes in door or frame faces where hardware was removed
- Card reader or kick plate added to a rated door after the fact
- Bottom clearance that grew when the flooring was replaced
Who needs one
If a building has rated door assemblies, the annual inspection requirement applies. In practice that means almost every commercial and institutional building, and four categories where it's asked about most:
- Schools. Rated corridor and stairwell doors throughout, high cycle counts, and an AHJ who asks.
- Healthcare. The most heavily inspected building type, with rated assemblies on nearly every corridor and the documentation expectations to match.
- Multifamily. Stairwell doors, unit entry doors into rated corridors, mechanical and trash rooms.
- Commercial and industrial. Rated separations, stair enclosures, and the doors between occupancies.
Service area
Field inspections are centered on Onondaga, Oswego, Cayuga, Madison, and Seneca counties, and buildings elsewhere in New York State are covered too. Larger portfolios across multiple buildings are worth scheduling together rather than one at a time.
Questions About Fire Door Inspection
- Is an annual fire door inspection actually required?
Yes. NFPA 80 requires fire door assemblies to be inspected and tested at least once a year, with a written record kept for the authority having jurisdiction.
- What fails most often?
Doors that close but don't latch, doors propped or held open with unapproved devices, painted-over labels, and gaps under the door that grew when the flooring changed.
- Can failures be fixed during the inspection?
Many can. Most failures are adjustment or parts — closers, latches, hold-opens, coordinators — not replacement.
- What do we get afterward?
A dated written record for every rated opening: what was inspected, what failed, and what was corrected.
- Who can perform the inspection?
NFPA 80 requires a person with knowledge and understanding of the operating components of the door being inspected.
Your insurer or AHJ may have its own expectations — worth checking before you schedule.
Related
Need the annual inspection on record?
Tell me roughly how many rated openings the building has and what documentation exists today. A free 15-minute call is usually enough to scope it.